Guardrails Report
Technical and operational frameworks for automated HVAC duct routing. Optimizing hospital infrastructure through deterministic engineering constraints and regulatory adherence.
Project Focus
Saudi MOH Facility
Agent Role
Duct Routing Autonomy
01 Executive Summary
"The AI agent must operate within a deterministic, rule-based framework to mitigate severe risks. This document defines hard constraints for regulatory standards (SBC 501, Saudi MOH), BIM protocols (ISO 19650), engineering thresholds, and spatial coordination hierarchies."
02. Regulatory Standards
-
ISO 19650: Must respect WIP/Shared/Published CDE states.
-
SBC 501 (Mechanical): Automatic FD/SD insertion at fire-rated penetrations.
-
MOH Healthcare: Strict 8m separation for air intakes; no combined exhaust for high-risk zones.
03. Spatial Hierarchy
04. Engineering Performance
Velocity & Friction
Material Constraints
Sterile Zones
304/316L Stainless Steel for post-HEPA
MRI Suites
Non-ferrous only (Aluminum/Non-magnetic)
05. Clinical Operations
Isolation Pressure Regimes
AII rooms require dedicated exhaust directly to roof. Zero cross-connection with general return air allowed.
Infection Control
Allocated spatial envelopes for HEPA filter housings (1000x1000x600mm) and UVGI modules in AHUs.
06. BIM & Data Protocols
LOD 350
Development Level
Exact dimensions, flanges, and hanger placeholders.
IFC 4x3
Interoperability
Native openBIM compatibility with Omniclass codes.
Internal Clash Logic
Unresolved clashes > 0 (excluding <10mm tolerance) trigger mandatory HITL (Human-in-the-Loop) review.
Architecture & ID
Dynamic integration with fit-out elements and structural constraints.
Structure
Zero penetration of shear walls/beams. Min 50mm clearance.
RCP Void
Strict routing within void space. Max 30° transitions for bulkheads.
Maintenance
600x600mm virtual 'keep-out' zones around all VCD/VAV units.